Airflow Range: 4,000~230,000 m³/h (2,353~135,294 CFM)
Total Pressure Range: 30~2,000 Pa (0.12~8.03 in.WG.)
Drive Type: Direct drive
Mounting Types: Base mounted/ Ceiling hung
Applications: General air supply and exhaust/ Explosion-proof air supply and exhaust / Positive pressure air supply/ Smoke removal
The fan shall be tested and certified in accordance with AMCA Standard 210 & 300, TUV EN 12101-3 for smoke application. AMCA Seal for (Efficiency Sound, Air Performance and Fan energy index FEI) shall be tagged on each fan before leaving the factory as a standard seal, for other seals shall be tagged on the fan according to application and customer needs.
The manufacturer shall obtain Production License for National Industrial Products and be certified by ISO 9001, ISO 14001, ISO 45001.
It shall be vane-axial fan with airfoil blades. The fan shall be direct driven and in a cylindrical structure. Behind the impeller in the cylindrical body, there shall be guiding vanes for airflow straightening. The guiding vane shall have a three-dimensional curved surface in line with flow field characteristics for better air performance and static efficiency.
The surface of the fan shall be polished to remove any protuberances, welding spatters, burrs, sharp edges and scrap iron. Then it shall undergo the processes of oil removal, pickling, and applying putty before being finished with electrostatic epoxy coatings processed under high temperature for strong adhesion. The surface shall be a level one without sags, cracks, cockles or detachment to avoid corrosion over a long period of time.
Fan Part | Description |
Impeller – Type M |
It shall be an axial impeller with airfoil blades of variable angles to ensure that right models can be selected for various operating conditions. The impeller shall have a vortex hub to avoid turbulence and airfoil blades of optimum air performance. Stable airflow and low noise shall be ensured at the maximum running speed. Die casted Aluminum, the hub and blades shall be strong enough to maintain operational reliability and safety at a speed 120% of the maximum speed. The impeller should be subject to dynamic balancing tests up to AMCA 204- G2.5 balance quality grade so that its operational stability can be improved and service life extended.
|
Fan Housing |
The fan housing shall be made of quality carbon steel and continuously welded and use lap joint flanges. For the fan housing with the impeller diameter of less than 500mm, the carbon steel thickness should be no less than 2mm, For the fan housing with the impeller diameter between 500 and 1000mm, the carbon steel thickness should be no less than 2.5mm; For the fan housing with the impeller diameter of over 1000mm, the carbon steel thickness should be no less than 3mm. All these are to ensure the fan’s operational safety and reliability over a long period of time and extend its service life.
|
Motor |
It shall be of B5 or B14 installation type. The motor is (IP55,IP56,…etc) rated as per specification with Class F Insulation (Class H Insulation for Smoke Removal) and Temperature Rise Class B. Lubrication-free ball bearings shall be used. The coefficient of power reserve of the selected motor shall be over 110% to ensure safe operation. As the motor is located inside the fan, it is the supplier that shall provide the appropriate external junction box based on the actual application.
|